Machine Model: WT2G
Following checks and corrections are applied during Validation and AutoCorrection.
- If Lp > 0.5*Ls is not possible then Lp = 0.5*Ls.
- If Ll > 0.8*Lpp is not possible then Ll = 0.8*Lpp.
- If 0 < Tpo < Mult*TimeStep then Tpo = Mult*TimeStep
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Model Equations and/or Block Diagrams
Parameters:
| Ls | Synchrounous reactance, (pu > 0) |
| Lp | Transient reactance (pu, > 0) |
| Ll | Stator leakage reactance (pu, > 0) |
| Ra | Stator resistance, pu |
| Tpo | Transient rotor time constant, sec |
| S1 | Saturation factor at 1.0 pu flux |
| S12 | Saturation factor at 1.2 pu flux |
| spdrot | Initial electrical rotor speed, p.u. of system frequency |
| Accel | Acceleration factor for initialization |